Schneider BMXMSP0200 2-axis pulse output, the maximum output frequency is 200KHZ, with 4 discrete inputs and 2 discrete auxiliary outputs
main information
Product Series
Modicon X80
product type
PTO module
Number of channels
2
Number of outputs
4
Digital input type
Sink type Yes source input conforming to IEC 61131-2 type 3
Sink type Yes Proximity switch and limit switch input conforming to IEC 61131-2 Type 3
Sink or source type Counter position input conforming to IEC 61131-2 type 3
Sink or source drive ready, emergency input conforming to IEC 61131-2 type 3
Input compatible
2-wire/3-wire proximity sensor 19.2…30 V conforming to IEC 947-5-2
Output compatibility
Signal converter (USIC)
RS422, 7 mA input
Source input, 5 V to 24 V
Output frequency
200 kHz <0.5 m with USIC and VW3M8210R05
100 kHz <5 m with the normal source input circuit
200 kHz <10 m with the RS422 compatible circuits
Additional information
Operating threshold
> 12 V supply voltage without error
> 8 V wrong power supply voltage
Input voltage
24 V DC
Input Current
4.3 mA
Ensure that the voltage status is "1"
>= 11 V
Current consumption
35 mA at 24 V DC pre-trigger
150 mA at 3.3 V DC typical
200 mA at 3.3 V DC maximum
Current status guarantee 1
>= 2 mA
Ensure that the voltage state is "0"
5 V
Current status guarantee 0
<= 1.5 mA
Response time
<200 µs for position completion input and drive ready input
<60 µs for source input and proximity switch input
(Output) Number of channels
1 pulse output
2 auxiliary output
Front drive voltage detection threshold
<8 V Wrong pre-trigger voltage Auxiliary output
<8 V Pre-trigger voltage without error Auxiliary output
> 14 V wrong pre-trigger voltage pulse output
> 14 V pre-trigger voltage error-free pulse output
The output voltage
24 V DC
Output voltage limit
19...30 V
Discrete output current
50 mA
Current per channel
0.4 A
maximum leakage current
0.05 mA at 0 state
Residual Pressure [Ures]
0.15 V in 1 state
Output response time
1.2...1.5 ms appearance
1.2...1.5 ms appearance
Load impedance
15000 Ω
Output overload protection
Use current limiter and electronic circuit breaker
Output short circuit protection
Use current limiter and electronic circuit breaker
Reverse polarity protection
Install diode output in reverse direction
Integrated input
Isolation between channels
non-isolated
Separation between primary and secondary
1500 Vrms
Insulation resistance
> 10 MΩ
Local signal indication
1 LED (green) Module operation (RUN):
1 LED (red) External fault (I/O):
1 LED (red) internal fault, module fault (ERR):
1 LED (green) Download (DL):
8 LEDs (green) Channel status (CH00):
8 LEDs (green) Channel status (CH01):
Electrical connections
2 terminal and 28 pin
Module classification
standard
certified product
CE
UL
CSA
RCM
EAC
Merchant ship
ATEX zone 2/22
IECEx zone 2/22
surroundings
Operating temperature
-25…70 °C
Derating factor
Without
Comply with the directive
2014/35/EU-low voltage directive
2014/30/EU-electromagnetic compatibility
2014/34/EU-ATEX directive
2012/19/EU-WEEE Directive
Standard
EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5
EN/IEC 61850-3
EN/IEC 60079-0
Environmental characteristics
Hazardous area Class 1 Class 2
Contact: Mr.wu
Phone: 0086+13808548642
Tel: 0086+13808548642
Add: 99 Luojiang District, Quanzhou, Fujian
Email: 190807896@qq.com