Schneider BMXDRC0805H Discrete module X80 - 8 NO/NC Type C - Isolated relays - 125 V DC/250 V AC - sev
main information
Product Series
Modicon X80
product type
Relay discrete output module
Application field
Used in harsh environments
Discrete output quantity
8 Conforms to EN/IEC 61131-2
Discrete output logic
Positive or negative
Discrete output voltage
5...125 V 5...150 V DC
24...240 V 19...264 V AC
Additional information
Electrical connections
40 way terminal block
Network frequency
50/60 Hz
Network frequency limit
47…63 Hz
Sensor power supply
5...150 V
19...264 V
Conventional thermal current [Ith]
4 A at <40 °C
3 A at <50 °C
2 A at <60 °C
1.2 A at <70 °C
Insulation resistance
> 10 MΩ 500 V DC
Power consumption W
3.6 W
Output response time
<= 10 ms activation
<= 13 ms off
Typical power consumption
40 mA at 3.3 V DC
101 mA at 24 V DC
MTBF reliability
2683411 H
Type of protection
External short circuit protection
External overload protection
External overvoltage protection, inductive load AC network
External overvoltage protection, inductive load DC network
Output overload protection
1 quick blow fuse for each channel or channel group
Output overvoltage protection
Discharge diode for each output DC
RC circuit for each output AC
ZNO surge limiter for each output AC
Output short circuit protection
1 quick blow fuse for each channel or channel group
Minimum switching current [Imin]
10 mA 5 V DC
Electrical life
AC-12: 200000 cycles on 48 VA 24 V on -25…60 °C
AC-12: 200000 times on 28.8 VA 24 V on 60…70 °C
AC-12: 300,000 cycles on 48 VA 48 V on -25…60 °C
AC-12: 300,000 cycles on 28.8 VA 48 V on 60…70 °C
AC-12: 150000 cycles on 96 VA 48 V on -25…60 °C
AC-12: 150000 cycles on 57.6 VA 48 V on 60…70 °C
AC-12: 300,000 cycles on 110 VA 100...120 V on -25...60 °C
AC-12: 300,000 cycles on 66 VA 100...120 V on 60...70 °C
AC-12: 150000 cycles on 220 VA 100...120 V on -25...60 °C
AC-12: 150000 cycles on 132 VA 100...120 V on 60...70 °C
AC-12: 300,000 cycles on 220 VA 200...250 V on -25...60 °C
AC-12: 300,000 cycles on 132 VA 200...250 V on 60...70 °C
AC-12: 150000 cycles on 500 VA 200...250 V on -25...60 °C
AC-12: 150000 cycles on 300 VA 200...250 V on 60...70 °C
AC-15: 700000 cycles on 10 VA 24 V on -25…60 °C (load factor 0.4)
AC-15: 700,000 cycles on 6 VA 24 V on 60…70 °C (load factor 0.4)
AC-15: 500000 cycles on 24 VA 24 V on -25…60 °C (load factor 0.4)
AC-15: 500000 cycles on 14.4 VA 24 V on 60…70 °C (load factor 0.4)
AC-15: 200000 times on 48 VA 24 V on -25…60 °C (load factor 0.4)
AC-15: 200000 times on 28.8 VA 24 V on 60…70 °C (load factor 0.4)
AC-15: 700000 cycles on 10 VA 48 V on -25…60 °C (load factor 0.4)
AC-15: 700000 cycles on 6 VA 48 V on 60…70 °C (load factor 0.4)
AC-15: 500000 cycles on 24 VA 48 V on -25…60 °C (load factor 0.4)
AC-15: 500000 cycles on 14.4 VA 48 V on 60…70 °C (load factor 0.4)
AC-15: 300,000 cycles on 48 VA 48 V on -25…60 °C (load factor 0.4)
AC-15: 300,000 cycles on 28.8 VA 48 V on 60…70 °C (load factor 0.4)
AC-15: 100000 cycles on 96 VA 48 V on -25…60 °C (load factor 0.4)
AC-15: 100000 cycles on 57.6 VA 48 V on 60…70 °C (load factor 0.4)
AC-15: 1000000 cycles on 10 VA 100...120 V on -25...60 °C (load factor 0.4)
AC-15: 1000000 cycles on 6 VA 100...120 V on 60...70 °C (load factor 0.4)
AC-15: 300000 cycles on 50 VA 100...120 V on -25...60 °C (load factor 0.4)
AC-15: 300,000 cycles on 30 VA 100...120 V on 60...70 °C (load factor 0.4)
AC-15: 200000 times on 110 VA 100...120 V on -25...60 °C (load factor 0.4)
AC-15: 200000 cycles on 66 VA 100...120 V on 60...70 °C (load factor 0.4)
AC-15: 70000 cycles on 220 VA 100...120 V on -25...60 °C (load factor 0.4)
AC-15: 70,000 cycles on 132 VA 100...120 V on 60...70 °C (load factor 0.4)
AC-15: 1000000 cycles on 10 VA 200...250 V on -25...60 °C (load factor 0.4)
AC-15: 1000000 cycles on 6 VA 200...250 V on 60...70 °C (load factor 0.4)
AC-15: 500000 cycles on 50 VA 200...250 V on -25...60 °C (load factor 0.4)
AC-15: 500000 cycles on 30 VA 200...250 V on 60...70 °C (load factor 0.4)
AC-15: 200000 cycles on 110 VA 200...250 V on -25...60 °C (load factor 0.4)
AC-15: 200000 cycles on 66 VA 200...250 V on 60...70 °C (load factor 0.4)
AC-15: 150000 cycles on 220 VA 200...250 V on -25...60 °C (load factor 0.4)
AC-15: 150000 cycles on 132 VA 200...250 V on 60...70 °C (load factor 0.4)
DC-12: 200000 times on 24 W 24 V on -25…60 °C
DC-12: 200000 times on 14.4 W 24 V on 60…70 °C
DC-12: 150000 cycles on 48 W 24 V on -25…60 °C
DC-12: 150000 cycles on 28.8 W 24 V on 60…70 °C
DC-12: 150000 cycles on 40 W 48...60 V on -25...60 °C
DC-12: 150000 cycles on 24 W 48...60 V on 60...70 °C
DC-12: 100000 cycles at 45 W 100...125 V at -25...60 °C
DC-12: 60000 cycles at 45 W 100...125 V at 60...70 °C
DC-13: 100000 cycles on 10 W 24 V on -25…60 °C
DC-13: 100000 cycles on 6 W 24 V on 60…70 °C
DC-13: 60000 cycles on 24 W 24 V on -25…60 °C
DC-13: 60000 cycles on 14.4 W 24 V on 60…70 °C
DC-13: 40000 cycles on 48 W 24 V on -25…60 °C
DC-13: 40000 cycles on 28.8 W 24 V on 60…70 °C
DC-13: 40000 cycles on 40 W 48...60 V on -25...60 °C
DC-13: 40000 cycles on 24 W 48...60 V on 60...70 °C
DC-13: 100000 cycles on 15 W 100...125 V on -25...60 °C
DC-13: 40000 cycles on 15 W 100...125 V on 60...70 °C
LED status
RUN: LED (green)
Channel diagnosis: 1 LED (green) per channel
ERR: LED (red)
I/O: LED (red)
Product Weight
0.189 kg
surroundings
IP protection level
IP20
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
Insulation performance
1780 V AC at 50/60 Hz for 1 minute
Anti-vibration
3 gn
Impact resistance
30 gn
Storage temperature
-40…85 °C
Operating temperature
-25…70 °C
Relative humidity
0…95% on -25…70 °C without condensation
Protection treatment
Three anti-coating
Working altitude
0...2000 m
2000...5000 m Yes
Contact: Mr.wu