Schneider BMXDRA0815 8-channel relay DC/AC output module, 125VDC/240VAC, isolation, 20-point terminal block
main information
Product Series
Modicon X80
product type
Relay discrete output module
Discrete output quantity
8 Conforms to EN/IEC 61131-2
Discrete output logic
positive
Discrete output voltage
24...240 V 19...264 V AC
24...125 V 5...150 V DC
Additional information
Electrical connections
20-way terminal
Network frequency
50/60 Hz
Network frequency limit
47…63 Hz
Sensor power supply
5...150 V
19...264 V
Conventional thermal current [Ith]
2 A
Insulation resistance
> 10 MΩ 500 V DC
Power consumption W
3.6 W
Output response time
<= 10 ms activation
<= 13 ms off
Typical power consumption
40 mA at 3.3 V DC
101 mA at 24 V DC
MTBF reliability
2683411 H
Protection type
External short circuit protection
External overload protection
External overvoltage protection, inductive load AC network
External overvoltage protection, inductive load DC network
Output overload protection
1 quick blow fuse for each channel or channel group
Output overvoltage protection
Discharge diode for each output DC
RC circuit for each output AC
ZNO surge limiter for each output AC
Output short circuit protection
1 quick blow fuse for each channel or channel group
Minimum switching current [Imin]
1 mA 5 V DC
Electrical life
AC-12: 200000 times on 48 VA 24 V on 0…60 °C
AC-12: 300000 cycles on 48 VA 48 V on 0…60 °C
AC-12: 150000 cycles on 96 VA 48 V on 0…60 °C
AC-12: 300,000 cycles on 110 VA 100...120 V on 0…60 °C
AC-12: 150000 cycles on 220 VA 100...120 V on 0...60 °C
AC-12: 300,000 cycles on 220 VA 200...250 V on 0…60 °C
AC-12: 150000 cycles on 500 VA 200...250 V on 0...60 °C
AC-15: 700000 cycles on 10 VA 24 V on 0…60 °C (load factor 0.4)
AC-15: 500000 cycles on 24 VA 24 V on 0…60 °C (load factor 0.4)
AC-15: 200000 times on 48 VA 24 V on 0…60 °C (load factor 0.4)
AC-15: 700000 cycles on 10 VA 48 V on 0…60 °C (load factor 0.4)
AC-15: 500000 cycles on 24 VA 48 V on 0…60 °C (load factor 0.4)
AC-15: 300000 cycles on 48 VA 48 V on 0…60 °C (load factor 0.4)
AC-15: 100000 cycles on 96 VA 48 V on 0…60 °C (load factor 0.4)
AC-15: 1000000 cycles on 10 VA 100...120 V on 0...60 °C (load factor 0.4)
AC-15: 300,000 cycles on 50 VA 100...120 V on 0...60 °C (load factor 0.4)
AC-15: 200000 times on 110 VA 100...120 V on 0...60 °C (load factor 0.4)
AC-15: 70,000 cycles on 220 VA 100...120 V on 0...60 °C (load factor 0.4)
AC-15: 1000000 cycles on 10 VA 200...250 V on 0...60 °C (load factor 0.4)
AC-15: 500000 cycles on 50 VA 200...250 V on 0...60 °C (load factor 0.4)
AC-15: 200000 times on 110 VA 200...250 V on 0...60 °C (load factor 0.4)
AC-15: 150000 cycles on 220 VA 200...250 V on 0...60 °C (load factor 0.4)
DC-12: 200000 times on 24 W 24 V on 0…60 °C
DC-12: 150000 cycles on 48 W 24 V on 0…60 °C
DC-12: 150000 cycles on 40 W 48...60 V on 0...60 °C
DC-12: 100000 cycles on 45 W 100...125 V on 0...60 °C
DC-13: 100000 cycles on 10 W 24 V on 0…60 °C
DC-13: 60000 cycles on 24 W 24 V on 0…60 °C
DC-13: 40000 cycles on 48 W 24 V on 0…60 °C
DC-13: 40000 cycles on 40 W 48...60 V on 0...60 °C
DC-13: 100000 cycles on 15 W 100...125 V on 0...60 °C
LED status
RUN: LED (green)
Channel diagnosis: 1 LED (green) per channel
ERR: LED (red)
I/O: LED (red)
Product Weight
0.169 kg
surroundings
IP protection level
IP20
Insulation performance
1780 V AC at 50/60 Hz 1 min
Anti-vibration
3 gn
Impact resistance
30 gn
Storage temperature
-40…85 °C
Operating temperature
0…60 °C
Relative humidity
0…95% at 60 °C without condensation
Working altitude
0...2000 m
2000...5000 m Yes