Schneider BMXCPS3522S Redundant power supply module X80-125 V DC-Safety
main information
Product Series
Modicon X80
product type
Power module
backplane compatibility
All backplanes
advanced diagnostics available via network
Redundant information
Redundancy test
Remaining life cycle
Temperature perception
Ascent duration
Main voltage
125 V
Input type
Direct current
Secondary power supply
18 W 3.3 V DC at -25…60 °C I/O module logic power supply
40 W 24 V DC at -25…60 °C I/O module power supply and processor 3.3V not loaded
Additional information
Main voltage limit
100...150 V
Input Current
600 A 125 V
Maximum current
60 A 125 V
I²t activation
2.5 A².s 125 V
It activates
0.09 A.s 125 V
MTBF reliability
871500 H
Type of protection
The internal fuse cannot be connected to the main circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short circuit protection for secondary circuit
Current at secondary voltage
1.67 A 24 V DC I/O module logic power supply
5 A 3.3 V DC I/O module power supply and processor
maximum power dissipation in W
8.5 W
LED status
Voltage status (OK): LED (green)
Redundancy normal: LED (green)
Power status: LED (green)
Control type
RESET button cold start
Electrical connections
1 connector 2-pin alarm relay
1 connector 5-pin line power, protective ground
Insulation resistance
>= 100 MΩ main circuit/ground
>= 100 MΩ primary/secondary
Product Weight
0.64 kg
surroundings
Resistance to instantaneous power failure
1 ms
Insulation performance
1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V main circuit/ground
Anti-vibration
3 gn
Impact resistance
15 gn
IP protection level
IP20
Comply with the directive
2014/30/EU-electromagnetic compatibility
2006/42/EC-machinery
2014/34/EU-ATEX directive
certified product
CE
UL
CSA
RCM
EAC
Merchant ship
ATEX zone 2/22
IECEx zone 2/22
TÜV
Standard
EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5
EN/IEC 61850-3
EN/IEC 60079-0
Environmental characteristics
Hazardous area Class 1 Class 2
Gas resistant class Gx meets ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust-proof class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant class 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforms to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Storage temperature
-40…85 °C
Operating temperature
-25…60 °C
Relative humidity
5…95% at 55 °C without condensation
Protection treatment
Three anti-coating
Working altitude
0...2000 m
2000...5000 m Yes
Contact: Mr.wu
Phone: 0086+13808548642
Tel: 0086+13808548642
Add: 99 Luojiang District, Quanzhou, Fujian
Email: 190807896@qq.com
Notes: All products enjoy a 6-month warranty