Schneider 140ATI03000C Analog input module Modicon Quantum-8 I thermocouple
main information
Product Series
Modicon Quantum automation platform
product type
Analog input module
Filter type
Notch filter-3 dB at 50/60 Hz
Single pole low pass-3 dB at 20 Hz
Additional information
Number of analog inputs
8
Address requirements
10 input words
Analog input type
Thermocouple:-210...760 °C for thermocouple J
Thermocouple:-270...1000 °C for thermocouple E
Thermocouple:-270...1370 °C for thermocouple K
Thermocouple:-270...400 °C for thermocouple T
Thermocouple:-50...1665 °C for thermocouple R
Thermocouple:-50...1665 °C for thermocouple S
Analog input resolution
16 bits
input resistance
> 1 MOhm
Absolute accuracy error
+/- 2 °C plus + 0.1% of reading Thermocouple E
+/- 2 °C plus + 0.1% of reading thermocouple J
+/- 2 °C plus + 0.1% of reading thermocouple K
+/- 2 °C plus + 0.1% of reading Thermocouple T
+/- 4 °C plus + 0.1% of reading Thermocouple R
+/- 4 °C plus + 0.1% of reading Thermocouple S
Linearity error
1 °C, 0.1 °C, 1 F, 0.1 F-210...760 °C
1 °C, 0.1 °C, 1 F, 0.1 F-270...1000 °C
1 °C, 0.1 °C, 1 F, 0.1 F-270...1370 °C
1 °C, 0.1 °C, 1 F, 0.1 F-270...400 °C
1 °C, 0.1 °C, 1 F, 0.1 F-50...1665 °C
Temperature deviation accuracy
0.15 μV/°C + 0.0015% of reading/°C maximum Low voltage level
common mode rejection
>-120 dB 50/60 Hz
Insulation between each channel and bus
1780 V AC for 60 s
2500 V DC for 60 s
Isolation between channels
300 V DC
220 V AC
Update time
1000 ms
Fault type
Disconnected
Overtacking scale
Logo
CE
Node cold compensation
Internal 0…60 °C
Local signal indication
1 LED (green) Bus communication in progress (active):
1 LED (red) for external fault
8 LEDs (green) for channel is turned on
8 LEDs (red) for channel fault
Demand bus current
280 mA
Power consumption W
1.5 W
Module classification
standard
Product Weight
0.3 kg
surroundings
Protection treatment
Conformal Coating Humiseal 1A33
Standards compliant
UL 508
CSA C22.2 No 142
certified product
CUL
FM, Category 1, Category 2
Anti-static discharge
4 kV contacts conforming to IEC 801-2
8 kV broadcast conforming to IEC 801-2
Anti-electromagnetic domain
10 V/m 80…1000 MHz conforming to IEC 801-3
Operating temperature
0…60 °C
Storage temperature
-40…85 °C
Relative humidity
95% non-condensing
Working altitude
<= 5000 m
Contact: Mr.wu
Phone: 0086+13808548642
Tel: 0086+13808548642
Add: 99 Luojiang District, Quanzhou, Fujian
Email: 190807896@qq.com
Notes: All products enjoy a 6-month warranty